5 |
0 |
R/W |
DOUT_WORDS
- 0: The DOUT_WORDS input is block based. Only
one value is input per block on DOUT_WORDS, and this specifies the number of LLRs in each
128-bit lane for a complete block (for example, a value of 16 on DOUT_WORDS indicates
that all 128 bits of each lane of DOUT should be used).
- 1: The DOUT_WORDS input is supplied for each AXI transaction on DOUT. For every AXI
transaction on DOUT there must be a corresponding transaction on DOUT_WORDS. If DOUT_WIDTH is set to use multiple lanes, then
DOUT_WORDS must provide a value for each 128-bit lane as given in the table in LLR Output
Words (DOUT_WORDS).
|
4:3 |
0 |
R/W |
DOUT: Width conversion applied to DOUT and DOUT_WORDS data
- 0: 1x128b
- 1: 2x128b
- 2: 4x128b
- 3: Reserved
|
2 |
0 |
R/W |
DIN_WORDS
- 0: The DIN_WORDS input is block based. Only
one value is input per block on DIN_WORDS, and this specifies the number of LLRs in each
128-bit lane for a complete block (for example, a value of 16 on DIN_WORDS indicates that
all 128 bits of each lane of DIN should be used).
- 1: The DIN_WORDS input is supplied for each AXI transaction on DIN. For every AXI
transaction on DIN there must be a corresponding transaction on DIN_WORDS. If DIN_WIDTH is set to use multiple lanes, then
DIN_WORDS must provide a value for each 128-bit lane as given in the table in Data Input
Control AXI4-Stream Slave (DIN_WORDS).
|
1:0 |
0 |
R/W |
DIN: Width conversion applied to DIN and DIN_WORDS data
- 0: 128b
- 1: 2x128b
- 2: 4x128b
- 3: Reserved
|
- This register should only be changed after reset when the interfaces are disabled.
|